Scrubber: "CEMS failure" alarm every 4 minutes, no alarm on the SICK analyser
EL-0055 · Solved · rating 0 · works for 0 engineers · occurred 01 Jan 2023
Source: /cases/el-0055
Symptoms#
- The scrubber panel shows "CEMS failure" about every 4 minutes. Sometimes there is no alarm for about 20 minutes, then it comes back.
- The CEMS itself shows no new alarm. Its status goes to Stop and the Failure lamp comes on for a couple of seconds. Then the status is Conditioning for 118 seconds, then back to Measurement.
Checked#
| Check | Result |
|---|---|
| "S035 Ref energy low" (Maintenance request), active for more than a year | Does not affect operation (maker's answer) |
| SFU filter | Replaced recently (changed every month) |
Diagnosis#
The gas sample outlet tube from the CEMS cabinet was pinched. The pressure was 755 hPa instead of the set 750 hPa.
Fix#
Straightened the tube. The pressure came down to the set value, 750 hPa.
Result#
No more "CEMS failure" alarms. Note that the CEMS sent the failure to the scrubber panel without showing any alarm of its own.