Siemens LOGO! fuel changeover: program loaded but does not run
EL-0058 · Solved · rating 0 · works for 0 engineers · occurred 18 May 2023
Source: /cases/el-0058
Symptoms#
- The automatic HFO/MDO changeover (valves and fuel heating) is controlled by a Siemens LOGO! 230RC with expansion modules.
- A "Control fail" alarm came up on the fuel page of the control PC.
- Expansion module A0A3 (DM8 230R, 6ED1 055-1FB00-0BA1) showed a red RUN/STOP LED.
- After a power restart, all modules showed red.
- The LOGO! had the program, but did not run it and did not switch any output relays.
Checked#
| Check | Result |
|---|---|
| Program | Deleted and restored from backup — no change |
| Bus contacts on the side of the modules | OK |
| Inputs | The LOGO! saw the inputs of all modules (removing a wire changed the input) |
There was no spare module on board.
Diagnosis#
Expansion module A0A3 was faulty. While it was on the bus, the LOGO! did not run the program.
Fix#
- Removed module A0A3 from the LOGO! bus.
- Moved its input wires to the next module, A0A4.
- Left the old A0A4 wires disconnected. They carried only the bypass valve position signals.
Result#
The LOGO! started and ran the program. Operation was partly restored: the valves can be opened in manual mode.