Siemens LOGO! fuel changeover: program loaded but does not run

Automation / PLCSiemens LOGO! 230RC with DM8 230R and AM2 expansion modulesControl fail

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • The automatic HFO/MDO changeover (valves and fuel heating) is controlled by a Siemens LOGO! 230RC with expansion modules.
  • A "Control fail" alarm came up on the fuel page of the control PC.
  • Expansion module A0A3 (DM8 230R, 6ED1 055-1FB00-0BA1) showed a red RUN/STOP LED.
  • After a power restart, all modules showed red.
  • The LOGO! had the program, but did not run it and did not switch any output relays.

Checked#

CheckResult
ProgramDeleted and restored from backup — no change
Bus contacts on the side of the modulesOK
InputsThe LOGO! saw the inputs of all modules (removing a wire changed the input)

There was no spare module on board.

Diagnosis#

Expansion module A0A3 was faulty. While it was on the bus, the LOGO! did not run the program.

The faulty DM8 230R module A0A3 with red RUN/STOP LED
The faulty DM8 230R module A0A3 with red RUN/STOP LED

Fix#

  1. Removed module A0A3 from the LOGO! bus.
  2. Moved its input wires to the next module, A0A4.
  3. Left the old A0A4 wires disconnected. They carried only the bypass valve position signals.
After the fix: LOGO! base, A0A4 and A0A5 in RUN (green); the faulty A0A3 set aside at top left
After the fix: LOGO! base, A0A4 and A0A5 in RUN (green); the faulty A0A3 set aside at top left

Result#

The LOGO! started and ran the program. Operation was partly restored: the valves can be opened in manual mode.