NMF deck crane: no POWER REQUEST after flooding, CPU blinks RUN/STOP

Deck MachineryAutomation / PLCNMF crane, Moeller XC-CPU201

Contents
  1. Symptoms
  2. Diagnosis
  3. Fix
  4. Result
  5. Comments · 0

Symptoms#

  • The cranes were badly flooded: slip rings and control panels. Slip rings and panels were cleaned and dried.
  • The cranes had been without power for 2 days.
  • Cranes 1 and 3 started. On crane 2 the POWER REQUEST lamp on the panel did not light.
  • On the main CPU the green LED between RUN and STOP blinked all the time. The manual says this means CPU stop.
  • Controller module A17 showed a red LED. On the other cranes all LEDs were normal.
  • The main CPU gives the signals to the relays for POWER REQUEST and other functions.
Main CPU Moeller XC-CPU201: RUN/STOP LED blinking
Main CPU Moeller XC-CPU201: RUN/STOP LED blinking
Module A17 with the red LED on
Module A17 with the red LED on

Diagnosis#

The main CPU had failed.

Fix#

  1. Switched off the power.
  2. Took the memory card out of the old CPU.
  3. Fitted a new battery in the new CPU.
  4. Installed the new CPU with the memory card.

Result#

The crane works. No program backup was needed.