NMF deck crane: no POWER REQUEST after flooding, CPU blinks RUN/STOP
EL-0063 · Solved · rating 0 · works for 0 engineers · occurred 20 Oct 2023
Source: /cases/el-0063
Symptoms#
- The cranes were badly flooded: slip rings and control panels. Slip rings and panels were cleaned and dried.
- The cranes had been without power for 2 days.
- Cranes 1 and 3 started. On crane 2 the POWER REQUEST lamp on the panel did not light.
- On the main CPU the green LED between RUN and STOP blinked all the time. The manual says this means CPU stop.
- Controller module A17 showed a red LED. On the other cranes all LEDs were normal.
- The main CPU gives the signals to the relays for POWER REQUEST and other functions.
Diagnosis#
The main CPU had failed.
Fix#
- Switched off the power.
- Took the memory card out of the old CPU.
- Fitted a new battery in the new CPU.
- Installed the new CPU with the memory card.
Result#
The crane works. No program backup was needed.