Teamtec OG400 incinerator: "Communication failure PLC - display" after battery change
EL-0005 · Solved · rating 0 · works for 0 engineers · occurred 05 Jul 2021
Source: /cases/el-0005
Symptoms#
- The PLC battery was replaced with the incinerator switched off from the mains.
- After switching on: "Communication failure PLC - display".
- All PLC data and settings were lost.
Diagnosis#
The PLC battery must be changed with the incinerator power ON. With the power off and the battery out, the PLC lost its settings.
Fix#
- Found the memory module with the incinerator settings. It had been supplied by the maker when the same problem happened before.
- Inserted the module into the PLC. The PLC loaded the settings automatically.
- Started the incinerator.
Result#
The incinerator works normally.