Incinerator will not light: thick white smoke, flame sensor drops out
EL-0060 · Solved · rating 0 · works for 0 engineers · occurred 23 Jun 2023
Source: /cases/el-0060
Symptoms#
- The incinerator would not light. The flame sensor lost the flame.
- Before, it had worked every day.
- The furnace had not been cleaned for a long time. Both chambers were full of ash, and all the air holes at the bottom were blocked. The furnace was cleaned out.
Checked#
- Flame sensor: it does see the flame when one burner nozzle fires, so it was not changed.
Diagnosis#
There are air pipes at the bottom of the furnace. They were open too wide. After the cleaning, too much air went in. This gave thick white smoke, and the smoke made the flame sensor lose the flame.
Before, the incinerator worked only because ash had blocked these air holes.
Fix#
Closed the air pipes at the bottom of the furnace a little.
Result#
The incinerator lit at once.
Comments · 0