Atlas incinerator will not burn sludge: no start signal to dosing pump

Incinerator & SewageAtlas

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • The incinerator would not burn sludge.
  • Chamber temperature rose normally and reached the set point for starting the sludge burner.
  • But the PLC gave no output signals: no "dosing pump ready to start", nothing to the frequency converter, the solenoids or the air.
  • Before this, the burner had gone out 3–4 times during dry docking.

Checked#

The frequency converter and the dosing pump were tested by simulating the PLC signals. Both worked normally at different speeds.

Diagnosis#

In the display settings, the control had been switched to test mode. The manual has no information about this; it was found by trial on the simple display panel.

Fix#

Switched the control from test mode back to normal operation in the display settings.

Result#

Sludge burning works again.