Atlas incinerator will not burn sludge: no start signal to dosing pump
EL-0093 · Solved · rating 0 · works for 0 engineers · occurred 10 Jan 2020
Source: /cases/el-0093
Symptoms#
- The incinerator would not burn sludge.
- Chamber temperature rose normally and reached the set point for starting the sludge burner.
- But the PLC gave no output signals: no "dosing pump ready to start", nothing to the frequency converter, the solenoids or the air.
- Before this, the burner had gone out 3–4 times during dry docking.
Checked#
The frequency converter and the dosing pump were tested by simulating the PLC signals. Both worked normally at different speeds.
Diagnosis#
In the display settings, the control had been switched to test mode. The manual has no information about this; it was found by trial on the simple display panel.
Fix#
Switched the control from test mode back to normal operation in the display settings.
Result#
Sludge burning works again.