Fire detection: fault on loop point 2.6, but all loop detectors test OK
EL-0094 · Solved · rating 0 · works for 0 engineers · occurred 17 Jan 2020
Source: /cases/el-0094
Symptoms#
- The fire detection panel showed a fault on loop 2, point 2.6.
- The ship was in a storm.
Checked#
| Check | Result |
|---|---|
| All connections on loop 2 | Re-crimped |
| All detectors on loop 2 (as per the drawing on hand) | OK |
Diagnosis#
Another drawing of the system showed more detectors. One of them was named 2.6a and was on the forecastle. It was not on the first drawing. From storm vibration this smoke detector had fallen off its base, and the fault came at once.
Fix#
Put detector 2.6a back on its base.
When a fault points to an address and the detector with that number is fine, look for a detector with a letter suffix (such as 2.6a) on the other system drawings.