Consilium CS4000: false fire alarm in cargo hold keeps coming back
EL-0033 · Solved · rating 0 · works for 0 engineers · occurred 04 May 2026
Source: /cases/el-0033
Symptoms#
- Fire alarm from a cargo hold zone, but there was no fire. The Fault LED was also lit.
- After a reset the alarm came back the next morning and then would not reset. A full system restart did not help.
- The alarm appeared each time the voltage at the isolator dropped below 15 V DC. The working range in the manual is 15–35 V DC.
Checked#
| Check | Result |
|---|---|
| Hold conditions | 26 °C, humidity not high, hold fans started |
| Isolator supply | 15 V DC present |
| Isolator loop in / loop out | 35 V DC each |
| Barrier in / out | 15 V DC each |
| Isolator voltage, watched for 30–40 min | 15.8–16.5 V DC |
| Hold detectors | Cleaned; some replaced with new ones — no change |
| Detector bases | Contacts tight, no oxidation |
| Cables in the hold | No visible damage |
Diagnosis#
One detector mounted in the bulkhead had been missed in all the earlier checks. Its LED was lit red. This faulty detector caused the false alarms.
Fix#
Replaced that detector.
Result#
No more false alarms.
Comments · 0
No comments yet.