MacGregor crane: slewing stops with "60 Joystick level error"

Deck MachineryMacGregor crane, MPC control cards60 Joystick level error (normal is 1,5 to 10,5V)

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • The slewing card showed error 60 "Joystick level error (normal is 1,5 to 10,5V)".
  • The crane stopped because of this error.

Checked#

  • Cleaned and tightened the joystick wires at the panel terminals MB:401, 402, 403, 404, 407 and 408.
  • Cleaned and tightened the contacts inside the joystick.
  • The error stayed.

Diagnosis#

The slewing joystick is a potentiometer. It gets its supply from the slewing MPC card ("SL") and sends its signal back to the same card.

TerminalSignal (from the manual)
MB:40112 V from MPC "SL"
MB:4026 V from MPC "SL"
MB:4030 V from MPC "SL"
MB:404Joystick input, 1.5–10.5 V, 6 V in neutral
MB:407 / MB:40824 V when the lever is moved to slew left / right

The wiring and the joystick were not the problem. The "SL" card itself was faulty.

The control rack has four MPC cards of the same type (hardware 314 3603-901, software MGX0201). The display on each card shows its function: Sc, Ho, Lu (luffing) and SL (slewing).

MacGregor MPC card rack: Sc, Ho, Lu and SL cards
MacGregor MPC card rack: Sc, Ho, Lu and SL cards

Fix#

Replaced the "SL" card with a working card of the same type. Do not pull a card while it is powered.

Result#

The crane worked normally with the replacement card.