Consilium CS4000: "IOM70 Synchronisation signal" fault
EL-0116 · Solved · rating +1 · works for 0 engineers · occurred 16 May 2026
Source: /cases/el-0116
Symptoms#
- Fault alarm on the water mist main panel: "(212) CENTRAL 1 IOM70 51 SYNCHRONISATION SIGNAL", with "PUMP CONTROL BOX - UNIT FAULT INPUTS".
- On the I/O M70 module: PS LED flashing yellow, COM LED green.
- A power reset did not help.
Diagnosis#
In the manual LED table, PS flashing yellow with COM green means "Boot-loader mode". The module was stuck in boot-loader mode.
Fix#
Replaced the I/O M70 module:
- Switch off the power.
- Remove the old module.
- Set the DIP switches on the new module the same as on the old one. Do not forget this step.
- Fit the new module, connect the wires and switch on the power.
No firmware or configuration work was needed.
Result#
The replacement went smoothly. The new module worked at once.