Eltek fire panel: "Fault in addressable loop", but all detectors test OK
EL-0061 · Solved · rating 0 · works for 0 engineers · occurred 20 Jul 2023
Source: /cases/el-0061
Contents
Symptoms#
- The panel showed FAULT CONDITION: "FAULT IN ADDRESSABLE LOOP: 01". The FAULT lamp was on.
- The loop worked: the detector test on this loop passed.
- The manual has no description of this fault.
- The fault had been there for some time, from before the crew change.
Diagnosis#
One detector had been connected with + and − swapped. The loop still worked, so only this fault showed.
The loop goes out from the panel board and comes back to it. There is no end-of-line resistor in this system.
Fix#
The loop has 87 detectors. A procedure from the maker (not in the manual) found the faulty one much faster than checking them one by one:
- Take out the loop out wires (+, −) at the panel (here TB 5, 6 in the DA panel; next test: TB 17, 18).
- Wait 1–2 minutes. The panel shows many faults, for example "No answer" from address No. 1 to No. 6.
- Check the voltage at the address where the faults end (No. 6 or No. 7). It should have no power.
- Check the connection on that detector base and connect it correctly. Here + and − were swapped.
- Check the voltage on the loop out wires: it should be 35 V DC / 28 V DC.
- Reconnect the wires to the panel and press RESET.