Eltek fire panel: "Fault in addressable loop", but all detectors test OK

Fire & SafetyEltekFAULT IN ADDRESSABLE LOOP: 01

Contents
  1. Symptoms
  2. Diagnosis
  3. Fix
  4. Comments · 0

Symptoms#

  • The panel showed FAULT CONDITION: "FAULT IN ADDRESSABLE LOOP: 01". The FAULT lamp was on.
  • The loop worked: the detector test on this loop passed.
  • The manual has no description of this fault.
  • The fault had been there for some time, from before the crew change.
Fire alarm panel: "Fault in addressable loop: 01"
Fire alarm panel: "Fault in addressable loop: 01"

Diagnosis#

One detector had been connected with + and − swapped. The loop still worked, so only this fault showed.

The loop goes out from the panel board and comes back to it. There is no end-of-line resistor in this system.

Fix#

The loop has 87 detectors. A procedure from the maker (not in the manual) found the faulty one much faster than checking them one by one:

  1. Take out the loop out wires (+, −) at the panel (here TB 5, 6 in the DA panel; next test: TB 17, 18).
  2. Wait 1–2 minutes. The panel shows many faults, for example "No answer" from address No. 1 to No. 6.
  3. Check the voltage at the address where the faults end (No. 6 or No. 7). It should have no power.
  4. Check the connection on that detector base and connect it correctly. Here + and − were swapped.
  5. Check the voltage on the loop out wires: it should be 35 V DC / 28 V DC.
  6. Reconnect the wires to the panel and press RESET.
Maker's sheet: how to find a loop open circuit / broken wire
Maker's sheet: how to find a loop open circuit / broken wire