Consilium CS4000: new manual call point gives "No answer"

Fire & SafetyConsilium CS4000No answer

Contents
  1. Symptoms
  2. Diagnosis
  3. Fix
  4. Result
  5. Comments · 0

Symptoms#

  • An old manual call point (P/N 11305) was replaced with the new type MCP-A, P/N 5200030-01A.
  • The system did not find the new unit: alarm "No answer" for its address, although the address was set correctly on the DIP switches.
  • Old-type call points come online at once when connected (hot-plug, as the manual says).
Old-type manual call point, P/N 11305
Old-type manual call point, P/N 11305
New MCP-A (P/N 5200030-01A): address DIP switches and terminals
New MCP-A (P/N 5200030-01A): address DIP switches and terminals

Diagnosis#

The new call point type does not work as hot-plug, although the manual says call points are hot-plug. The system sees it only after a full restart.

Fix#

  1. Connect the loop to terminals 5 and 6 of the new call point.
  2. Restart the whole fire detection system: switch off all its supplies — battery, emergency switchboard and main switchboard — then switch on again.

Result#

After the full restart the new call points work. Without it, the "No answer" alarm stays.