Consilium CS4000: new manual call point gives "No answer"
EL-0084 · Solved · rating 0 · works for 0 engineers · occurred 21 Sept 2025
Source: /cases/el-0084
Symptoms#
- An old manual call point (P/N 11305) was replaced with the new type MCP-A, P/N 5200030-01A.
- The system did not find the new unit: alarm "No answer" for its address, although the address was set correctly on the DIP switches.
- Old-type call points come online at once when connected (hot-plug, as the manual says).
Diagnosis#
The new call point type does not work as hot-plug, although the manual says call points are hot-plug. The system sees it only after a full restart.
Fix#
- Connect the loop to terminals 5 and 6 of the new call point.
- Restart the whole fire detection system: switch off all its supplies — battery, emergency switchboard and main switchboard — then switch on again.
Result#
After the full restart the new call points work. Without it, the "No answer" alarm stays.