Hyundai HV switchboard: generator VCB tripped, no reset button
EL-0117 · Solved · rating +1 · works for 0 engineers · occurred 08 Apr 2026
Source: /cases/el-0117
Symptoms#
- The generator engine shut down on lube oil. HIMAP showed reverse power, and the generator VCB (6600 V) tripped.
- The breaker could not be reset at the breaker. There is no reset button and no handle on it, only an emergency open button.
Diagnosis#
The HV VCB has no settings or trip memory of its own. All protection settings and trips are in the HIMAP-BC relay of that generator panel.
Fix#
Reset the trip on the HIMAP-BC of that generator panel.
Result#
The trip was reset, and the breaker could be used again.