Search

Cases

0 rating0 commentsTerasaki PMS: generator will not parallel in auto, "ACB non close"TroubleshootingElectrical · Terasaki PMS · ACB non closeWhen a generator was put in parallel in automatic mode, the alarm "ACB non close" came up. The breaker did not close and the engine stayed running with no load. Frequency and voltage were the same as…Anonymous · 4 y0 rating0 commentsGenerator will not come off the bus at stop: "Stop failure", reverse powerTroubleshootingElectrical · Stop failureThe undervoltage (UV) coil of a generator air circuit breaker (ACB) was burnt. To keep the breaker usable, the UV coil plunger was held in with its mechanical lock. The generator synchronised and…Anonymous · 1 y0 rating0 commentsEmergency generator breaker closes and opens again at once, no tripTroubleshootingElectrical · Schneider Masterpact NT06 H2, Micrologic 5.0 AThe emergency generator breaker would not stay closed on the emergency switchboard bus, in both auto and manual mode. On "close" the breaker clicked and closed. The green "closed" indication was on…Anonymous · 4 y