Log inJoin
Search

Cases

0 rating0 commentsEmergency generator: insulation drops to 0.1 MΩ at every startTroubleshootingElectrical · Low insulation 440 VEvery time the emergency generator started, the 440 V insulation monitor fell to 0.1–0.2 MΩ. After 2–3 hours of running, the reading slowly came back to normal (5 MΩ and higher). The ship had been…Anonymous · 7 y0 rating0 commentsShipboard electric motors: routine maintenance checks and testsKnowledgeElectricalPreventive maintenance of shipboard electric motors comes down to daily attention plus a few periodic checks and tests. The best thing I know is an electro-technical officer (ETO) on board who…Anonymous · 4 y