Emergency generator: insulation drops to 0.1 MΩ at every start
EL-0002 · Solved · rating 0 · works for 0 engineers · occurred 10 Aug 2019
Source: /cases/el-0002
Symptoms#
- Every time the emergency generator started, the 440 V insulation monitor fell to 0.1–0.2 MΩ.
- After 2–3 hours of running, the reading slowly came back to normal (5 MΩ and higher).
- The ship had been drifting for two weeks in very humid weather. The emergency generator room has natural ventilation only.
Checked#
| Check | Result |
|---|---|
| Alternator windings to earth (megger) | 56 MΩ — OK |
| Between phases | 55 MΩ — OK |
| Terminal box: tightness, water, salt | Tight, clean, dry |
| Cable route to the emergency switchboard | No damage, no moisture |
| Insulation monitor (swapped with another) | Same readings |
| Space heater switch | ON |
Diagnosis#
The space heater was switched on, but its supply connection had been disconnected. The heater never worked, so the windings took up moisture while the generator stood. Running warmed and dried them — that is why the insulation recovered after a few hours.
Fix#
Reconnected the space heater supply.
Result#
Insulation is normal at start.