Emergency generator: insulation drops to 0.1 MΩ at every start

ElectricalLow insulation 440 V

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • Every time the emergency generator started, the 440 V insulation monitor fell to 0.1–0.2 MΩ.
  • After 2–3 hours of running, the reading slowly came back to normal (5 MΩ and higher).
  • The ship had been drifting for two weeks in very humid weather. The emergency generator room has natural ventilation only.

Checked#

CheckResult
Alternator windings to earth (megger)56 MΩ — OK
Between phases55 MΩ — OK
Terminal box: tightness, water, saltTight, clean, dry
Cable route to the emergency switchboardNo damage, no moisture
Insulation monitor (swapped with another)Same readings
Space heater switchON

Diagnosis#

The space heater was switched on, but its supply connection had been disconnected. The heater never worked, so the windings took up moisture while the generator stood. Running warmed and dried them — that is why the insulation recovered after a few hours.

Fix#

Reconnected the space heater supply.

Result#

Insulation is normal at start.