Emergency generator trips on blackout test, then will not close on the bus

ElectricalSchneider Electric ComPacT NSX630

Contents
  1. Symptoms
  2. Diagnosis
  3. Fix
  4. Comments · 0

Symptoms#

  • Blackout test from the main switchboard: the supply to the emergency switchboard was switched off.
  • The emergency generator started, closed onto the bus and took the load.
  • After 5–10 minutes it stopped (tripped). No alarms.
  • Restarted 10–20 s later, it no longer closed onto the bus.
  • In test mode (key switch) everything worked well and the generator held the load.

Diagnosis#

The fault was in the undervoltage release (UVT, MN/UVR) of the breaker, a Schneider Electric ComPacT NSX630. The plastic lever of the UVT mechanism inside the breaker was badly worn.

MN/UVR slot of the NSX630: the worn plastic lever is circled
MN/UVR slot of the NSX630: the worn plastic lever is circled

Because of this the breaker always stayed in the ON position. It should open when the breaker on the main switchboard side is switched off.

Fix#

  1. Temporary: pressed the UVT coils back into place. After this the breaker worked.
  2. Permanent: replace the breaker. The UVT coil can be ordered and changed separately, but the plastic lever is part of the breaker itself. The company decided to replace the whole breaker.
  3. Note: this NSX type has not been produced since 2024. A newer model replaces it.
The MN/UVR undervoltage release, 220–240 V, 10 VA — the coil can be replaced separately
The MN/UVR undervoltage release, 220–240 V, 10 VA — the coil can be replaced separately