Emergency generator runs but its breaker will not close on blackout
EL-0013 · Solved · rating 0 · works for 0 engineers · occurred 19 May 2023
Source: /cases/el-0013
Symptoms#
- Emergency generator load test: the MSB–ESB transfer breaker was opened.
- The emergency generator started normally.
- Its breaker did not close onto the ESB bus.
Checked#
| Check | Result |
|---|---|
| Emergency generator breaker taken out and opened | Undervoltage release (UVR) coil, 110 V, burnt |
| 110 V applied to the UVR coil | No movement |
Diagnosis#
The UVR coil must be energised before the breaker can close. With the coil burnt, the breaker cannot close onto the bus.
Fix#
- As a test, the breaker was put back without the UVR coil.
- On the next test it closed onto the ESB bus at once. This confirmed the burnt coil as the cause.
- A new 110 V UVR coil is needed. Without it the breaker has no undervoltage protection, so do not leave the breaker running without the coil.