Log inJoin

Emergency generator runs but its breaker will not close on blackout

Electrical

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Comments · 0

Symptoms#

  • Emergency generator load test: the MSB–ESB transfer breaker was opened.
  • The emergency generator started normally.
  • Its breaker did not close onto the ESB bus.

Checked#

CheckResult
Emergency generator breaker taken out and openedUndervoltage release (UVR) coil, 110 V, burnt
110 V applied to the UVR coilNo movement
Emergency generator breaker opened up: the MN/UVR undervoltage release coil (110–130 V, 10 VA) is at the bottom, next to the trip unit
Emergency generator breaker opened up: the MN/UVR undervoltage release coil (110–130 V, 10 VA) is at the bottom, next to the trip unit

Diagnosis#

The UVR coil must be energised before the breaker can close. With the coil burnt, the breaker cannot close onto the bus.

Fix#

  1. As a test, the breaker was put back without the UVR coil.
  2. On the next test it closed onto the ESB bus at once. This confirmed the burnt coil as the cause.
  3. A new 110 V UVR coil is needed. Without it the breaker has no undervoltage protection, so do not leave the breaker running without the coil.

Comments · 0

No comments yet.