Emergency generator will not crank on batteries that test OK

Auxiliary EngineElectrical

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • The emergency generator did not start on the electric starter, from the remote panel or from the local panel on the engine.
  • The engine turned over once or twice, then stopped cranking. The start relay kept clicking: first attempt 0.5 s after the start button, then a new attempt every 3 s, until the panel power was switched off.
  • With the hydraulic starter the engine started normally.
  • Batteries: 200 Ah, 24 V set, 2.5–3 years old, cranking current up to 1400 A. Their built-in indicators showed white (replace).
  • Two months before, the same fault happened. A new start timer was fitted then and the generator started again, so this time the relays and timers were checked first.

Checked#

CheckResult
Battery voltage at rest / after load28.5 V / 28.2 V — looked OK
Load tester on each batteryBack to 14 V after 10–15 s — looked OK
Voltage on the batteries during cranking (multimeter)Fell from 28 V to 5 V

Diagnosis#

The batteries were worn out. Rest voltage and the load test looked normal, but under the starter load the voltage collapsed.

Fix#

Charged new spare lifeboat batteries (100 Ah, 850 A) and fitted them in place of the old set.

Result#

The generator starts on the electric starter. During cranking the voltage now drops only to 15 V.