Cummins NTA855 emergency generator: speed hunts ±30 rpm after a cold start
EL-0085 · Solved · rating 0 · works for 0 engineers · occurred 23 Sept 2025
Source: /cases/el-0085
Symptoms#
- On the first cold start, speed hunted by about ±30 rpm at 1800 rpm (frequency by about 0.5 Hz).
- After a restart (sometimes the 2nd or 3rd) it ran smoothly, and further starts were fine. A few hours later the hunting came back.
- Load made no difference: it carried 100 % load for 4 hours and hunted in the same range.
- First noticed during an on-load test. The fuel tank had silt at the bottom, near the suction.
Checked#
| Check | Result |
|---|---|
| Fuel filters | Changed — no change |
| Fuel in tank | Drained, new fuel — no change |
| Air leaks in fuel system | None |
| Exhaust while hunting | Clean, no smoke |
| Magnetic pick-ups | Cleaned, gap set — no change |
| Strainer on fuel pump | Cleaned |
| Two non-return valves in fuel line | Opened, perfect condition |
| Fuel shut-off valve | In correct position |
| Cables and connections | OK |
Diagnosis#
The fault was in the speed control: the speed control card in the generator starting panel, or the actuator on the fuel pump. The maker pointed to the actuator.
On two other ships with the same symptoms, replacing only the speed control card cured it. One had the same generator; there, a new fuel pump and injectors had not helped.
Fix#
Service replaced both the fuel pump actuator and the speed control card.
Result#
The generator runs at steady speed.