Cummins NTA855 emergency generator: speed hunts ±30 rpm after a cold start

Auxiliary EngineCummins NTA855-D(M)

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • On the first cold start, speed hunted by about ±30 rpm at 1800 rpm (frequency by about 0.5 Hz).
  • After a restart (sometimes the 2nd or 3rd) it ran smoothly, and further starts were fine. A few hours later the hunting came back.
  • Load made no difference: it carried 100 % load for 4 hours and hunted in the same range.
  • First noticed during an on-load test. The fuel tank had silt at the bottom, near the suction.

Checked#

CheckResult
Fuel filtersChanged — no change
Fuel in tankDrained, new fuel — no change
Air leaks in fuel systemNone
Exhaust while huntingClean, no smoke
Magnetic pick-upsCleaned, gap set — no change
Strainer on fuel pumpCleaned
Two non-return valves in fuel lineOpened, perfect condition
Fuel shut-off valveIn correct position
Cables and connectionsOK
Electric actuator on the fuel pump (the two wires with blue terminals)
Electric actuator on the fuel pump (the two wires with blue terminals)

Diagnosis#

The fault was in the speed control: the speed control card in the generator starting panel, or the actuator on the fuel pump. The maker pointed to the actuator.

On two other ships with the same symptoms, replacing only the speed control card cured it. One had the same generator; there, a new fuel pump and injectors had not helped.

Cummins speed control card, P/N 3044196 (ACT = actuator, MPU = magnetic pick-up)
Cummins speed control card, P/N 3044196 (ACT = actuator, MPU = magnetic pick-up)

Fix#

Service replaced both the fuel pump actuator and the speed control card.

Result#

The generator runs at steady speed.