Weishaupt Monarch burner sprays fuel as soon as the fan starts

BoilerWeishaupt Monarch

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • Fuel sprayed from the nozzle as soon as the burner fan motor started, during pre-purge.
  • It should spray only after purge, when the air damper closes, together with ignition.
  • The burner started and ran.
  • Same on the first and the second nozzle (tested one at a time, with the solenoids swapped).

Checked#

CheckResult
Solenoid valves and control (electrical side)Switch correctly and on time
Fuel pump pressure on diesel oil22 bar

Diagnosis#

The nozzle block was taken apart. There was scoring between the ball and the nozzle, so the nozzle did not shut off.

Nozzle block of the burner, with the manual page for the RL/RMS regulation system
Nozzle block of the burner, with the manual page for the RL/RMS regulation system

Fix#

Replaced the scored parts.

Result#

The burner works normally.