Caterpillar 3408 generator will not start after blackout
EL-0014 · Solved · rating 0 · works for 0 engineers · occurred 30 May 2023
Source: /cases/el-0014
Symptoms#
- The generator engine stopped and caused a blackout. Dirty fuel filters had let air into the fuel system.
- After the filters were changed, the engine cranked on the air starter but did not start.
Checked#
| Check | Result |
|---|---|
| Fuel filters | Replaced |
| Start solenoid | OK |
| Power at the local panel | Present |
Diagnosis#
Air was still in the fuel system. Fuel pressure was too low for the engine to fire.
Fix#
- Primed the fuel system with the hand pump, 50–60 strokes.
- Kept pumping the hand pump while the starter was cranking the engine.
Result#
The engine started only when the hand pump was worked during cranking. Priming alone was not enough.