Alfa Laval separator: alarm A85 (MT60 fault), water content shows only dashes

PurifierAlfa LavalA85 (MT60 fault)

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • Separator with a water content transducer. The transducer had problems for about two weeks.
  • The transducer board was replaced with a new one. After that, alarm A85 (MT60 fault) came up.
  • The old board was fitted back — same alarm.
  • The capacitance reading was about 300 pF. The water content (%) showed only dashes, as if the transducer saw nothing.

Checked#

CheckResult
New transducer boardAlarm A85
Old transducer board refittedSame alarm — the board was not the cause

Diagnosis#

The sensor in the pipe was heavily fouled. It had been reported as checked, but it was not really cleaned.

Fix#

Took the sensor out of the pipe and cleaned it to bright metal.

Result#

The alarm cleared and the transducer worked again.