Norimos 1000: "Signal syst. power F." alarm and all ventilation stops

ElectricalFire & SafetyNoris Norimos 1000SIGNAL SYST.POWER F.

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Comments · 0

Symptoms#

  • The alarm panel showed "SIGNAL SYST.POWER F." (signal system power failure).
  • Right after it, all ventilation stopped.
  • The ship was rolling.
Norimos 1000 alarm panel with "SIGNAL SYST.POWER F." alarm
Norimos 1000 alarm panel with "SIGNAL SYST.POWER F." alarm

Checked#

  • 24 V supply to the alarm panel: present.

Diagnosis#

There were two separate faults at the same time:

  1. Alarm: on the emergency switchboard, the breaker "Signal swbd" had tripped.
  2. Ventilation stop: it came from the CO2 system. During rolling, a limit switch in the CO2 system slipped off its plate, and the CO2 system stopped all ventilation.

Fix#

  1. Reset the "Signal swbd" breaker on the emergency switchboard.
  2. Set the CO2 system limit switch back on its plate.