MAN ME: exporting MOP event logs for remote troubleshooting

Main EngineAutomation / PLCMAN ES ME (electronically controlled), example engine 6S60ME-C

Contents
  1. Scope
  2. Safety
  3. Tools & parts
  4. Steps
  5. Check after
  6. Comments · 0

Scope#

This is how I export the Event Log and the HCU, HPS and Cylinder Events from the MOP of a MAN ES (formerly MAN Diesel & Turbo) ME engine, to send to a remote troubleshooter. There are two parts:

  • Procedure A: export the Event Log (alarm and event history).
  • Procedure B: export HCU, HPS and Cylinder Events.

The steps follow the MAN guide "Data Collection for Troubleshooting", rev. 5, reference EEO9/THSK/2018-01-03, pages 14 to 19 of 34 (section 3 and section 4.1). Section 4.2 (bulk export from the "MAD" folder) and the rest of the guide are not covered here. I don't have software versions or the differences between MOP screens.

Safety#

The guide pages I use give no safety notes. The steps use only the MOP screens and a USB stick.

Tools & parts#

  • One empty USB stick.
  • Access to MOP-A or MOP-B for the Event Log.
  • Access to MOP-B for HCU/HPS/Cylinder Events.

Steps#

Procedure A — Event Log (either MOP)

  1. On MOP-A or MOP-B, open Alarms > Event Log.
  2. If you need only part of the log, press "Time Span Filter". Choose the time period and press "Apply". For the full log, do not use the filter.
  3. Press "Export".
  4. Put the empty USB stick into the MOP.
  5. Press "Save". The time to save depends on how many events you export; a big log can take some time. Wait until it finishes.

Procedure B — HCU/HPS/Cylinder Events (MOP-B only)

  1. On MOP-B, open Troubleshooting > HCU/HPS Events. These events are not on MOP-A.
  2. An event can be recorded in two ways:
    • automatically, when an alarm starts the recording;
    • manually, by the operator. HCU, HPS and Cylinder events are all collected in the same way.
  3. To record an event manually, press "Log Manually". Then select one cylinder or more. After a short time, the new log shows in the list on the left side.
  4. To export, put the empty USB stick into MOP-B.
  5. Select the event in the list.
  6. Press "Export", then press "Save".
  7. If you need many files, note that all of them are in the "MAD" folder. The guide explains this in section 4.2, which I don't cover here.

Check after#

  • Check that the exported files are on the USB stick before you send them.
  • I record events about once a month in normal running, and also every time there is a problem. Regular records help the troubleshooter and give a baseline to compare with.
  • I also record MOP graphs at several loads while the engine is in good condition, and learn how to read them. In my experience, a healthy baseline makes faults much easier to find.

Example — exhaust valve position overshoot

CheckResult
EngineMAN 6S60ME-C
Exhaust valve position graphSignal overshoot (jump) seen
Operating modesOvershoot seen in all modes
Engine runningNo effect
Exhaust gas temperaturesNormal

This overshoot is normal. The valve opens as it should, and damping force acts on it. Because of this force, the valve comes back to a higher position. This damping is usually found on high-force exhaust valves. No fault was found or repaired.