0 rating0 commentsCaterpillar 3408 generator will not start after blackoutTroubleshootingAuxiliary Engine · Caterpillar 3408The generator engine stopped and caused a blackout. Dirty fuel filters had let air into the fuel system. After the filters were changed, the engine cranked on the air starter but did not start.Anonymous · 3 y0 rating0 commentsEmergency generator runs but its breaker will not close on blackoutTroubleshootingElectricalEmergency generator load test: the MSB–ESB transfer breaker was opened. The emergency generator started normally. Its breaker did not close onto the ESB bus.Anonymous · 3 y0 rating0 commentsEmergency generator trips on blackout test, then will not close on the busTroubleshootingElectrical · Schneider Electric ComPacT NSX630Blackout test from the main switchboard: the supply to the emergency switchboard was switched off. The emergency generator started, closed onto the bus and took the load. After 5–10 minutes it…Anonymous · 6 mo0 rating0 commentsEmergency generator breaker closes and opens again at once, no tripTroubleshootingElectrical · Schneider Masterpact NT06 H2, Micrologic 5.0 AThe emergency generator breaker would not stay closed on the emergency switchboard bus, in both auto and manual mode. On "close" the breaker clicked and closed. The green "closed" indication was on…Anonymous · 4 y0 rating0 commentsGenerator engine fails on non-OEM bearings run to OEM intervals (Kommandor Susan)IncidentAuxiliary Engine · Caterpillar 3516B-TA · ER fire alarm, blackoutDiesel-electric vessel on sea trials, just out of the lock at Leith with a pilot on board. DG1 and DG4 were on line. The C/E heard a change in engine note on one generator, then a loud bang. The fire…Anonymous · 6 mo0 rating0 commentsEngine room flooding from a corroded sea water pipe at the strainer (Oliver Hazard Perry)IncidentAuxiliary Engine · John Deere diesel generator · AC power fault alarm on fire alarm panel, blackoutSail training tall ship (128 ft), two Caterpillar C12 propulsion engines, two John Deere DGs (99 kW). Moored, one crewmember on board. Shore power breakers kept tripping, so the port DG ran…Anonymous · 7 mo0 rating0 commentsGenerator con-rod seizes and holes the block: oil run far past interval (Ocean Navigator)IncidentAuxiliary Engine · Caterpillar 3516B · ER fire alarm, AE2 low LO pressure and oil filter plugged, blackoutAE2 on a coastal cruise ship (Caterpillar 3516B, 1,800 rpm) had run its LO for more than 5,000 h and its filter elements for 3,329 h. Both should be changed at 1,000 h (LO longer only under…Anonymous · 1 y0 rating0 commentsAux engine room fire: slipped fuel pump coupling and exhaust leak (Finnmaster)IncidentAuxiliary Engine · Mitsubishi S12R · ER smoke alarm, then blackoutRo-ro leaving Hull with a pilot on board. AE1 had just been paralleled with AE2. Eight minutes after leaving the berth, smoke was detected in the aux engine room. Both AE2 exhaust temperature gauges…Anonymous · 1 y0 rating0 commentsThermal oil fire from a failing pump bearing, water mist did not work (Pride of Hull)IncidentPumps · Allweiler NTT 80-200 · ER fire alarm, zone "Oil treatment pumps"Ro-ro passenger ferry, outbound in the Humber. Thermal oil (Texatherm 32, winter set point 170 °C) carried heat from the economisers and a boiler. Circulation pump #1 was on duty. The fire panel…Anonymous · 4 y0 rating0 commentsStandard bearing shell on an undersize journal: con-rods break out (Ocean Guardian)IncidentAuxiliary Engine · Caterpillar 3516B · No alarm; loud bang, then smoke and fire in ERDiesel-electric offshore supply vessel, four Caterpillar 3516B main DGs (1,990 kW each). All four were overhauled by shore technicians in early 2022. On sea trials, DG3 had run about 4 h since…Anonymous · 3 y0 rating0 commentsMAN 48/60: con-rod small end breaks after bad bush renewal (Finlandia Seaways)IncidentMain Engine · MAN 12V48/60 · Crankcase oil mist high, No. 6 main bearing temp highRo-ro at sea, single MAN 12V48/60 at 500 rpm, 110 662 running hours. The on-watch 3/E was in the purifier room when he heard loud metallic knocking. The bridge felt heavy vibration and saw pitch and…Anonymous · 5 y0 rating0 commentsMain engine fuel filters burst with both return valves shut (Sandy Ground)IncidentMain Engine · EMD 12V-710 (710GC/L12ME23B) · High fuel filter dP, then low fuel pressure on all four MEsStaten Island ferry, four EMD MEs at 92 % load, 884 people on board. The oilers spent over 40 minutes turning valves to balance the two FO day tanks. In the end, the NTSB concluded, both FO return…Anonymous · 2 y