Hyundai generator: no voltage at start after a 440 V insulation alarm

ElectricalHyundai HFC7

Contents
  1. Symptoms
  2. Checked
  3. Diagnosis
  4. Fix
  5. Result
  6. Comments · 0

Symptoms#

  • The 440 V insulation reading started to jump between 0 and infinity.
  • Three generators were on the bus. Two were taken off, only No. 3 was left.
  • Next day generator No. 1 was started, but it did not build up voltage. The switchboard showed 0 V.

Checked#

CheckResult
Generator terminal box (covers off)Burnt-off wires on the reactor (L1) and on two current transformers
Burnt wires restored, engine startedStill no voltage
Burnt wire ends on the reactor (L1) terminal strip
Burnt wire ends on the reactor (L1) terminal strip

Diagnosis#

Two wires from the busbars to the reactor had chafed through their insulation and were shorting.

Chafed wires between the busbars and the reactor
Chafed wires between the busbars and the reactor

Fix#

Replaced the two chafed wires.

Result#

The generator builds up voltage and works normally.