Search

Cases

0 rating0 commentsKangrim boiler: "Flame failure" alarm while stopped, will not resetTroubleshootingBoiler · Kangrim · Flame failureFLAME FAILURE alarm came up while the boiler was stopped (not firing). The alarm could not be reset. A restart did not help.Anonymous · 2 y0 rating0 commentsGenerator will not come off the bus at stop: "Stop failure", reverse powerTroubleshootingElectrical · Stop failureThe undervoltage (UV) coil of a generator air circuit breaker (ACB) was burnt. To keep the breaker usable, the UV coil plunger was held in with its mechanical lock. The generator synchronised and…Anonymous · 1 y0 rating0 commentsScrubber: "CEMS failure" alarm every 4 minutes, no alarm on the SICK analyserTroubleshootingOther · SICK CEMS · CEMS failureThe scrubber panel shows "CEMS failure" about every 4 minutes. Sometimes there is no alarm for about 20 minutes, then it comes back. The CEMS itself shows no new alarm. Its status goes to Stop and…Anonymous · 3 y0 rating0 commentsScania generator (DEC2): fires 2 or 3 times at start, then fuel is cut offTroubleshootingAuxiliary Engine · Scania, DEC2 digital engine controlThe diesel generator cranks and fires 2–3 times, as if trying to start. Then the fuel supply stops and the engine does not start. Fuel comes back only after the DEC2 digital engine control system…Anonymous · 6 y0 rating0 commentsNorimos 1000: "Signal syst. power F." alarm and all ventilation stopsTroubleshootingElectrical · Noris Norimos 1000 · SIGNAL SYST.POWER F.The alarm panel showed "SIGNAL SYST.POWER F." (signal system power failure). Right after it, all ventilation stopped. The ship was rolling.Anonymous · 7 y