Search

Cases

0 rating0 commentsProvision plant compressor does not stop at pump-down, overcurrent tripTroubleshootingRefrigeration & HVACThe suction line has two low pressure switches: one stops the compressor, the other opens the unloader valve. When all cold room solenoid valves closed and suction pressure fell, the stop switch did…Anonymous · 7 y0 rating0 commentsHyundai steering gear: pump stops 4 seconds after start from the bridgeTroubleshootingSteering Gear · HyundaiIn the evening the running steering gear pump stopped, and the standby pump started. Started from the bridge (autopilot), the pump motor ran for about 4 seconds and then stopped. No alarms on the…Anonymous · 3 y0 rating0 commentsWeishaupt Monarch burner: random "Air combustion low" at startTroubleshootingBoiler · Weishaupt Monarch · Air combustion lowThe burner tripped only at boiler start, two or three times a day. The alarm changed: sometimes "Air combustion low", sometimes "Flame failure". It was random: no alarm for 10 hours, then up to five…Anonymous · 4 y0 rating0 commentsOceanGuard BWTS: "EUT Power Abnormal" 10 s after startTroubleshootingBallast System · OceanGuard · EUT Power Abnormal AlarmThe BWTS worked normally 3 days before. Now, about 10 seconds after start, the alarm "EUT Power Abnormal Alarm" came up and the system stopped. The EUT power unit got its supply: LEDs on all modules…Anonymous · 3 y0 rating0 commentsNabtesco governor: main engine will not go above 66 rpm, SCAVEN. LIMIT lamp onTroubleshootingMain Engine · Nabtesco governor control unit · M/E GOVERNOR SYSTEM ABNRThe main engine would not run faster than 66 rpm (Half Ahead). Scavenge air pressure was 0.2 bar. The auxiliary blowers were still running. On the governor control unit the SCAVEN. LIMIT lamp was on.…Anonymous · 3 y0 rating0 commentsScania generator (DEC2): fires 2 or 3 times at start, then fuel is cut offTroubleshootingAuxiliary Engine · Scania, DEC2 digital engine controlThe diesel generator cranks and fires 2–3 times, as if trying to start. Then the fuel supply stops and the engine does not start. Fuel comes back only after the DEC2 digital engine control system…Anonymous · 6 y0 rating0 commentsCO2 system: leaking cylinder valves release the whole bank (Eddystone, Red Eagle)IncidentFire & Safety · Schmöle K85-50 (Eddystone), DAB D10963 with D10964 actuator (Red Eagle) · CO2 release alarm, hissing in CO2 roomTwo UK ro-ro ships, same failure: nobody touched the CO2 release, but a bank emptied itself into the CO2 room. Eddystone was in the Southern Red Sea, ambient 32 °C. The CO2 release alarm sounded with…Anonymous · 8 y0 rating0 commentsWeishaupt Monarch burner sprays fuel as soon as the fan startsTroubleshootingBoiler · Weishaupt MonarchFuel sprayed from the nozzle as soon as the burner fan motor started, during pre-purge. It should spray only after purge, when the air damper closes, together with ignition. The burner started and…Anonymous · 6 y0 rating0 commentsAux boiler explosion: waxy MGO, then fan restart into a gassy furnace (Manhattan Bridge)IncidentBoiler · "" · Aux boiler emergency trip (Furnace flame-eye abnormal)A 13,900 TEU container ship was berthing at Felixstowe in winter. The auxiliary boiler (rotary cup burner) had been on MGO for three days for the ECA. It tripped four times between 17:30 and 19:51.…Anonymous · 8 y0 rating0 commentsKangrim boiler: "Flame failure" at the end of the ignition timeTroubleshootingBoiler · Kangrim · Flame failureComposite boiler. It had run in manual for more than a week. When it was switched to auto, the "Flame failure" alarm came. The burner starts and the flame burns. The alarm comes at the moment the…Anonymous · 5 y0 rating0 commentsAalborg thermal oil boiler: no fuel from the nozzle at ignitionTroubleshootingBoiler · Aalborg, LAL burner controlAfter a safety alarm test the boiler stopped and did not start again. The coil of the recirculation (return) solenoid valve had burnt. It had run hot for a long time: it looked melted and its wiring…Anonymous · 1 y0 rating0 commentsThermal oil fire from a failing pump bearing, water mist did not work (Pride of Hull)IncidentPumps · Allweiler NTT 80-200 · ER fire alarm, zone "Oil treatment pumps"Ro-ro passenger ferry, outbound in the Humber. Thermal oil (Texatherm 32, winter set point 170 °C) carried heat from the economisers and a boiler. Circulation pump #1 was on duty. The fire panel…Anonymous · 4 y