▲0 rating0 commentsHyundai generator: no voltage at start after a 440 V insulation alarmTroubleshootingElectrical · Hyundai HFC7The 440 V insulation reading started to jump between 0 and infinity. Three generators were on the bus. Two were taken off, only No. 3 was left. Next day generator No. 1 was started, but it did not…Anonymous · 4 y▲0 rating0 commentsGenerator will not come off the bus at stop: "Stop failure", reverse powerTroubleshootingElectrical · Stop failureThe undervoltage (UV) coil of a generator air circuit breaker (ACB) was burnt. To keep the breaker usable, the UV coil plunger was held in with its mechanical lock. The generator synchronised and…Anonymous · 1 y▲1 rating0 commentsHyundai HV switchboard: generator VCB tripped, no reset buttonTroubleshootingElectrical · Hyundai HIMAP-BCThe generator engine shut down on lube oil. HIMAP showed reverse power, and the generator VCB (6600 V) tripped. The breaker could not be reset at the breaker. There is no reset button and no handle…Anonymous · 7 mo▲0 rating0 commentsEmergency generator runs but its breaker will not close on blackoutTroubleshootingElectricalEmergency generator load test: the MSB–ESB transfer breaker was opened. The emergency generator started normally. Its breaker did not close onto the ESB bus.Anonymous · 3 y▲0 rating0 commentsEmergency generator breaker closes and opens again at once, no tripTroubleshootingElectrical · Schneider Masterpact NT06 H2, Micrologic 5.0 AThe emergency generator breaker would not stay closed on the emergency switchboard bus, in both auto and manual mode. On "close" the breaker clicked and closed. The green "closed" indication was on…Anonymous · 4 y▲0 rating0 commentsEmergency generator: insulation drops to 0.1 MΩ at every startTroubleshootingElectrical · Low insulation 440 VEvery time the emergency generator started, the 440 V insulation monitor fell to 0.1–0.2 MΩ. After 2–3 hours of running, the reading slowly came back to normal (5 MΩ and higher). The ship had been…Anonymous · 7 y▲0 rating0 commentsScania generator (DEC2): fires 2 or 3 times at start, then fuel is cut offTroubleshootingAuxiliary Engine · Scania, DEC2 digital engine controlThe diesel generator cranks and fires 2–3 times, as if trying to start. Then the fuel supply stops and the engine does not start. Fuel comes back only after the DEC2 digital engine control system…Anonymous · 6 y▲0 rating0 commentsYanmar generator: HT cooling water outlet 6 °C hotter than on the other engineTroubleshootingAuxiliary Engine · Yanmar (450 kW)Two Yanmar 450 kW generators in parallel, about 300 kW each. Engine HT inlet HT outlet Engine 1 76 °C 80 °C Engine 2 76 °C 86 °CAnonymous · 2 y▲0 rating0 commentsDEIF PPM-3: busbar voltage read too low, generator will not auto-synchroniseTroubleshootingAutomation / PLC · DEIF PPM-3The DEIF PPM-3 controller of one generator measured the busbar voltage lower than it really was. The PMS saw a voltage fault. Auto synchronising was not possible, only manual. When the measured…Anonymous · 2 y▲0 rating0 commentsEmergency generator will not crank on batteries that test OKTroubleshootingAuxiliary EngineThe emergency generator did not start on the electric starter, from the remote panel or from the local panel on the engine. The engine turned over once or twice, then stopped cranking. The start…Anonymous · 4 y▲0 rating0 commentsCaterpillar 3408 generator will not start after blackoutTroubleshootingAuxiliary Engine · Caterpillar 3408The generator engine stopped and caused a blackout. Dirty fuel filters had let air into the fuel system. After the filters were changed, the engine cranked on the air starter but did not start.Anonymous · 3 y▲0 rating0 commentsEmergency generator trips on blackout test, then will not close on the busTroubleshootingElectrical · Schneider Electric ComPacT NSX630Blackout test from the main switchboard: the supply to the emergency switchboard was switched off. The emergency generator started, closed onto the bus and took the load. After 5–10 minutes it…Anonymous · 6 mo▲0 rating0 commentsTerasaki PMS: generator will not parallel in auto, "ACB non close"TroubleshootingElectrical · Terasaki PMS · ACB non closeWhen a generator was put in parallel in automatic mode, the alarm "ACB non close" came up. The breaker did not close and the engine stayed running with no load. Frequency and voltage were the same as…Anonymous · 4 y▲0 rating0 commentsCummins NTA855 emergency generator: speed hunts ±30 rpm after a cold startTroubleshootingAuxiliary Engine · Cummins NTA855-D(M)On the first cold start, speed hunted by about ±30 rpm at 1800 rpm (frequency by about 0.5 Hz). After a restart (sometimes the 2nd or 3rd) it ran smoothly, and further starts were fine. A few hours…Anonymous · 1 y▲0 rating0 commentsYanmar generator: low LO pressure shutdown 5 minutes after startTroubleshootingAuxiliary Engine · YanmarAfter start, LO pressure was normal (4.8 bar), then slowly fell. After 5–6 minutes at most, the engine shut down on low LO pressure. The differential pressure indicator on the automatic LO filter…Anonymous · 4 y▲0 rating0 commentsAMS Totem Plus: ME Alpha Lubricator alarms go into inhibitTroubleshootingAutomation / PLC · Totem Plus IMACSAt sea, all ME Alpha Lubricator alarms on the AMS (about 6 channels) went into inhibit by themselves. Real alarms on the Alpha Lubricator panel did not come to the AMS. Alpha Lubricator solenoid…Anonymous · 8 mo▲0 rating0 commentsAlfa Laval plate FWG: high brine temperature (60 °C) and low outputTroubleshootingFresh Water Generator · Alfa Laval (plate type)Low fresh water output and brine temperature up to 60 °C. Cleaning the plates did not help. Vacuum and heating water were normal. Readings, the same before and after cleaning: Reading Value Heating…Anonymous · 10 mo