▲0 rating0 commentsGenerator will not come off the bus at stop: "Stop failure", reverse powerTroubleshootingElectrical · Stop failureThe undervoltage (UV) coil of a generator air circuit breaker (ACB) was burnt. To keep the breaker usable, the UV coil plunger was held in with its mechanical lock. The generator synchronised and…Anonymous · 1 y▲0 rating0 commentsAlfa Laval PA605 will not start after emergency stop is releasedTroubleshootingPurifier · Alfa Laval PA605 · Emergency button pressThe emergency stop button was pressed. After the button was released, the pump and the separator would not start. The alarm "Emergency button press" stayed on.Anonymous · 2 y▲0 rating0 commentsProvision plant compressor does not stop at pump-down, overcurrent tripTroubleshootingRefrigeration & HVACThe suction line has two low pressure switches: one stops the compressor, the other opens the unloader valve. When all cold room solenoid valves closed and suction pressure fell, the stop switch did…Anonymous · 7 y▲0 rating0 commentsNorimos 1000: "Signal syst. power F." alarm and all ventilation stopsTroubleshootingElectrical · Noris Norimos 1000 · SIGNAL SYST.POWER F.The alarm panel showed "SIGNAL SYST.POWER F." (signal system power failure). Right after it, all ventilation stopped. The ship was rolling.Anonymous · 7 y▲0 rating0 commentsHyundai steering gear: pump stops 4 seconds after start from the bridgeTroubleshootingSteering Gear · HyundaiIn the evening the running steering gear pump stopped, and the standby pump started. Started from the bridge (autopilot), the pump motor ran for about 4 seconds and then stopped. No alarms on the…Anonymous · 3 y▲0 rating0 commentsMitsubishi deck crane will not start after a limit switch stopTroubleshootingDeck Machinery · MitsubishiThe crane limit switches were being tested during a class survey. A limit switch tripped and the crane stopped. After that the crane would not start at all. There were no alarms.Anonymous · 1 y▲0 rating0 commentsMacGregor crane: alarm 93 "Encoder wrong position", crane stopsTroubleshootingDeck Machinery · MacGregor · 93 Encoder wrong positionAlarm 93 "Encoder wrong position" on the hoisting and luffing MPC. After one MPC was replaced, the alarm still came, but the crane could be operated. An hour later the alarm came again and the crane…Anonymous · 4 y▲0 rating0 commentsSEA-Mate B500 blender stops after blending, blend not dischargedTroubleshootingMain Engine · Marine Fluid Technology SEA-Mate Blender B500In auto mode the unit mixes the oils, then stops and stays stopped. It should open the valve and pump the blend on, but it does not. No alarm.Anonymous · 3 y▲0 rating0 commentsNMF deck crane: no POWER REQUEST after flooding, CPU blinks RUN/STOPTroubleshootingDeck Machinery · NMF crane, Moeller XC-CPU201The cranes were badly flooded: slip rings and control panels. Slip rings and panels were cleaned and dried. The cranes had been without power for 2 days. Cranes 1 and 3 started. On crane 2 the POWER…Anonymous · 3 y▲0 rating0 commentsKangrim boiler: "Flame failure" alarm while stopped, will not resetTroubleshootingBoiler · Kangrim · Flame failureFLAME FAILURE alarm came up while the boiler was stopped (not firing). The alarm could not be reset. A restart did not help.Anonymous · 2 y▲0 rating0 commentsBallast valve remote control: half the valves stop responding, no alarmTroubleshootingBallast System · Utsuki valve remote control, Yokogawa FA-M3 PLCAbout half of the hydraulic ballast valves stopped responding, all at the same time. No reaction from the ballast console or from the local control panel. No alarms. The valves could still be moved…Anonymous · 6 y▲0 rating0 commentsEmergency generator: all alarms when the rack bracket is releasedKnowledgeAuxiliary EngineAfter a manual (emergency) start, the fuel rack is held by a locking bracket. If this bracket is released while the engine runs, the engine stops at once and all alarms come up together.Anonymous · 7 y▲0 rating0 commentsTwo-stroke main engine: jobs to do while stopped in port or at anchorKnowledgeMain Engine · MAN ES ME / MCThis is my checklist of jobs to plan when the two-stroke main engine is stopped in port or at anchor and there is a good chance to do the work. It leaves out inspections that are due by running…Anonymous · 4 y▲0 rating0 commentsRolls-Royce steering gear: one pump stops the rudder at 10° to one sideTroubleshootingSteering Gear · Rolls-RoyceWith one of the two pumps, the rudder would not go more than 10° to one side. Same in follow-up and non-follow-up. It stopped at exactly 10° every time, from any starting position. Pushing the…Anonymous · 7 y▲0 rating0 commentsMacGregor crane: slewing stops with "60 Joystick level error"TroubleshootingDeck Machinery · MacGregor crane, MPC control cards · 60 Joystick level error (normal is 1,5 to 10,5V)The slewing card showed error 60 "Joystick level error (normal is 1,5 to 10,5V)". The crane stopped because of this error.Anonymous · 6 y▲0 rating0 commentsPods stuck at 90° after overspeed trip and a latched water-leak stop (Spirit of Discovery)IncidentPropulsion & Thrusters · Siemens SISHIp eSiPOD (SiPOD-M10) · Pod water leakage stop (WLS) sequence alarm, then propeller overspeedCruise ship with two Siemens eSiPOD pods (6,500 kW each, no rudder), crossing the Bay of Biscay in force 8–9 wind and 8–9 m waves. At 12:30 the port pod gave a WLS sequence alarm. Very soon after, it…Anonymous · 8 mo▲0 rating0 commentsHFO transfer pump: start relay chatters, pump will not start in manualTroubleshootingPumpsWhen Start is pressed, relay 4 in the starter crackles and buzzes. The main contactor does not pull in. The main contactor is new. With one output wire of the control circuit disconnected, the pump…Anonymous · 2 y▲0 rating0 commentsSiemens LOGO! fuel changeover: program loaded but does not runTroubleshootingAutomation / PLC · Siemens LOGO! 230RC with DM8 230R and AM2 expansion modules · Control failThe automatic HFO/MDO changeover (valves and fuel heating) is controlled by a Siemens LOGO! 230RC with expansion modules. A "Control fail" alarm came up on the fuel page of the control PC. Expansion…Anonymous · 3 y▲0 rating0 commentsDiesel oil bunkering: tank overflow through a taped vent, engine room fire (Stride)IncidentBoiler · MAN B&W 7S70MC Mk6 · Diesel oil seen dripping from upper ER; no tank high-level alarm recordedGeneral cargo ship alongside at LaPorte, Texas, taking 80 mt of LSMGO into the port and starboard double-bottom DO tanks. The C/E and 3/E ran the bunkering from the ECR, with both fill valves open.…Anonymous · 1 y▲0 rating0 commentsWhy anchors and anchor chains are lost or damagedKnowledgeDeck MachineryAnchors and chains are lost or damaged through a mix of technical wear, operational mistakes and use beyond the design limits of the equipment. This is a general note, not one fault case. When…Anonymous · 4 y▲0 rating0 commentsAux boiler explosion: waxy MGO, then fan restart into a gassy furnace (Manhattan Bridge)IncidentBoiler · "" · Aux boiler emergency trip (Furnace flame-eye abnormal)A 13,900 TEU container ship was berthing at Felixstowe in winter. The auxiliary boiler (rotary cup burner) had been on MGO for three days for the ECA. It tripped four times between 17:30 and 19:51.…Anonymous · 8 y▲0 rating0 commentsMain engine: gas bubbles in the fuel system, fuel pressure jumpingTroubleshootingMain EngineAir (gas) bubbles in the main engine fuel oil system. Small bubbles stayed all the time. Fuel pressure was jumping.Anonymous · 1 y▲0 rating0 commentsWestfalia OSD 60-91: bowl does not close, ejection monitoring alarmTroubleshootingPurifier · Westfalia OSD 60-91 · Ejection monitoringTwo main engine LO separators stopped one after the other on the ejection monitoring alarm. On both, the bowl did not close at all. No discharge either, not even a small one. No. 1 stopped 1,000…Anonymous · 2 y▲0 rating0 commentsMAN B&W ES main engine: precautions for long low-load runningKnowledgeMain Engine · MAN B&W ESMAN Service Letter SL09-511/MTS gives 10% load as the lowest load for continuous running of a MAN B&W ES two-stroke main engine, and running in this range needs precautions. These are the precautions…Anonymous · 4 y▲0 rating0 commentsMain engine fuel filters burst with both return valves shut (Sandy Ground)IncidentMain Engine · EMD 12V-710 (710GC/L12ME23B) · High fuel filter dP, then low fuel pressure on all four MEsStaten Island ferry, four EMD MEs at 92 % load, 884 people on board. The oilers spent over 40 minutes turning valves to balance the two FO day tanks. In the end, the NTSB concluded, both FO return…Anonymous · 2 y▲0 rating0 commentsMAN ME: internal leak test on the hydraulic systemProcedureMain Engine · MAN ES ME-type main engineThis procedure is for MAN ES main engines with electronic control (ME type). It covers the hydraulic power supply (HPS) pumps, the hydraulic cylinder units (HCU) and the safety and accumulator block.…Anonymous · 4 y▲0 rating0 commentsAux engine room fire: slipped fuel pump coupling and exhaust leak (Finnmaster)IncidentAuxiliary Engine · Mitsubishi S12R · ER smoke alarm, then blackoutRo-ro leaving Hull with a pilot on board. AE1 had just been paralleled with AE2. Eight minutes after leaving the berth, smoke was detected in the aux engine room. Both AE2 exhaust temperature gauges…Anonymous · 1 y▲0 rating0 commentsMain air compressor will not start, contactor does not pull inTroubleshootingCompressed AirOne main air compressor was opened up for overhaul. Then the other one stopped starting, both in auto and in manual. Pressing Start did nothing.Anonymous · 7 y▲0 rating0 commentsRolls-Royce steering gear: "Hydraulic lock" alarm at every small rudder movementTroubleshootingSteering Gear · Rolls-Royce · Hydraulic lock"Hydraulic lock" alarm on the steering gear. It started after a service in dry dock. At first it came now and then. Sometimes it cleared by itself, sometimes tightening the contacts helped. Later it…Anonymous · 2 y▲0 rating0 commentsBoiler water level DP transmitter shows a wrong level after drydockTroubleshootingBoilerAfter drydock the boiler water level DP transmitter stopped showing the right level. The reading made no sense. Before drydock it worked. Nobody said they had touched it.Anonymous · 4 y